APC UPS Setup

How to set up UPS monitoring via USB, for APC UPS models.
  1. Plug in the USB cable (dur)

  2. Edit the UPS service in TrueNas:

    2.1: Choose USB driver with closest match to APC UPS model, and choose correct USB device (usually something like /dev/ugenX.X) and set UPS name to simply ups

    2.2: DO NOT check Remote Monitor

    2.3: Add Monitor user and password, copy same info into the extra users section in this format (note brackets!):

    [{username}]
    	password = {password}
    	actions = set
    	actions = fsd
    	instcmds = all
    

    2.4: Set shutdown to "UPS Reaches Low Battery", set command to: shutdown -p +1 "System is shutting down due to low UPS battery!"

    2.5: DO NOT set up email alerts! (otherwise you get two sets for each event due to system alerting!)

    2.6: Add MAXAGE 25 to the "Auxilary Parameters (upsd.conf)" box (prevents occasional 'connection to UPS lost' errors)

  3. Enable the service!

  4. Check box to auto-start service.

Checking UPS status and changing parameters remotely:
  1. Check status of UPS (get all stats):
    upsc ups@localhost
    
  2. List commands that can be run from the terminal for a particular UPS:
    upscmd -u [username] -p [password] -l ups@localhost
    
  3. Run a command on a UPS:
    upscmd -u [username] -p [password] ups@localhost command.name.here
    
Typical commands: